Form: Orion-OE742-31-VAVZ-ZCAP-Sub-01C.doc Page 1 of 1
Description
The OE742-31-VAVZ VAV/Zone
Controller Actuator Package with
Power/Comm connectors pro-
vides a new solution for zone
damper applications. The new
package includes a VAV/Zone
Actuator and a VAV/Zone Con-
troller mounted in a plastic enclo-
sure. An optional conduit cover is
also available that mounts over
the control terminals for installa-
tions requiring conduit connec-
tions. The VAV/Zone Controller
Actuator Package is designed for
left- or right-hand mounting on a
VAV Terminal unit. Each package
comes standard with a right-hand
label and the actuator positioned
for right-hand use. For left-hand
units, the actuator can be rotated
180 degrees by removing two
screws that secure it to the enclo-
sure, rotating the damper actua-
tor, and re-fastening the actuator
to the enclosure. A left-hand label
is also supplied that can be ap-
plied over the right-hand label for
left-hand applications.
Mounting
The VAV/Zone Actuator package
is very easy to mount on your
terminal unit. It is installed by
simply loosening the damper
shaft u-bolt on the actuator and sliding the entire Zone Controller Actuator Package Assembly over the terminal unit’s damper
shaft, tightening the actuator u-bolt around the damper shaft, and inserting a self-tapping screw into the anti-rotation bushing
located at the opposite end of the enclosure base. Detailed mounting and installation instructions are provided with each
package. A conduit enclosure is available as an option which provides conduit knockouts and encloses the electrical connec-
tions for applications where code requirements mandate conduit be used for low voltage electrical wiring.
OE742-31-VAVZ VAV/Zone
Controller Actuator Package
Technical Data OE742-31-VAVZ
VAV/Zone Controller Actuator Package
Zone Controller: Outputs:
Supply Power 24 VAC (1) RJ-45 Cable Connection For Auxiliary Relay Board
Power Consumption 6 VA Maximum (1) RJ-45 Cable Connection To Damper Actuator
Operating Tempera-
ture
10F to 149F
(1) Molex Connector For Power/Comm Out
Operating Humidity 90% RH Non-Condensing
Features:
Communications RS-485 – 9600 Baud Programming Port Mini-DIN Jr. Port
Enclosure Material Fire Rated ABS Plastic
Inputs:
Zone Controller Factory Mounted Inside The Enclosure
(1) RJ-45 Cable Connection For Digital Temperature
Or Analog Temperature
Zone Actuator Factory Mounted To The Enclosure
Actuator Rating 35 in/lbs (6 ft
2
Damper Area Max.)
(2) Auxiliary Terminals For Duct Temperature Sen-
sor
Labeling Right Hand & Left Hand
(1) Molex Connector For Power/Comm In Airflow Ports Barbed Tube Fittings (PI Versions Only)
WattMaster reserves the right to change specifications without notice.
Three Year Warranty
Seitenansicht 0
1 2 3 4 5 6 ... 39 40

Inhaltsverzeichnis

Seite 1 - Controller Actuator Package

Form: Orion-OE742-31-VAVZ-ZCAP-Sub-01C.doc Page 1 of 1 Description The OE742-31-VAVZ VAV/Zone Controller Actuator Package with Power/Comm connectors

Seite 2 - OE742-32-VAVZ VAV/Zone

Form: Orion-OE520XX-T-RndDmpr-Sub-01G Page 1 of 2 Description The OE520-XX-T Round Pressure Dependent Zone Damper Assembly with terminal connector

Seite 3 - OE744-31-VAVZ VAV/Zone

Form: Orion-OE520XX-T-RndDmpr-Sub-01G Page 2 of 2 VAV/Zone Damper Sizing Use a load program to determine the peak load for each zone. These calcula

Seite 4 - OE744-32-VAVZ VAV/Zone

FormOrion-OE521XX-M-RndDmpr-Sub-01G Page 1 of 2 Description The OE521-XX-M Round Pressure Independent Zone Damper Assembly with modular connectors

Seite 5 - Outputs: Inputs:

FormOrion-OE521XX-M-RndDmpr-Sub-01G Page 2 of 2 Zone Damper Sizing Use a load program to determine the peak load for each zone. These calculations

Seite 6 - OE282 - Damper Actuator

Form: Orion-OE521XX-T-RndDmpr-Sub-01G Page 1 of 2 Description The OE521-XX-T Round Pressure Independent Zone Damper Assembly with terminal connect

Seite 7 - Zone Damper Actuator

Form: Orion-OE521XX-T-RndDmpr-Sub-01G Page 2 of 2 Zone Damper Sizing Use a load program to determine the peak load for each zone. These calculation

Seite 8 - OE520-XX-M Round P.D

Form: Orion-OE522-RDBypDmpr-Sub-01F Page 1 of 2 Description The OE522-XX Round Bypass Damper Assembly, consists of a round air damper with a bypass

Seite 9

Form: Orion-OE522-RDBypDmpr-Sub-01F Page 2 of 2 Bypass Damper Sizing Because the zones in an Orion System are controlled using variable air volume,

Seite 10 - Zone Damper

Form: Orion-OE523-RdSlaveDmpr-Sub-01F Page 1 of 2 Description The OE523-XX Round Slaved Zone Damper Assembly, consists of a round air damper, actuat

Seite 11 - Zone Damper

Form: Orion-OE523-RdSlaveDmpr-Sub-01F Page 2 of 2 Slaved Zone Damper Sizing Use a load program to determine the peak load for each zone. These cal

Seite 12 - OE521-XX-M Round P.I

Form: Orion-OE742-32-VAVZ-ZCAP-Sub-01B.doc Page 1 of 1 Description The OE742-32-VAVZ VAV/Zone Controller Actuator Package with Terminal Block connect

Seite 13

Form: Orion-OE524-XX-PD-RndPDDmpr-Sub-01A Page 1 of 2 Description The OE524-XX-PD Round Pressure Dependent Zone Damper consists of a Round Air Dampe

Seite 14

Form: Orion-OE524-XX-PD-RndPDDmpr-Sub-01A Page 2 of 2 Using the maximum acceptable velocity for a branch duct (typi-cally 1000-1500 FPM for minima

Seite 15

Form: Orion-OE524-XX-PI-RndPIDmpr-Sub-01A Page 1 of 2 Description The OE524 Round Pressure Independent Zone Damper consists of a Round Air Damper w

Seite 16 - Damper Assembly

Form: Orion-OE524-XX-PI-RndPIDmpr-Sub-01A Page 2 of 2 With pressure independent systems it is possible to exceed this rule by up to 50%. However

Seite 17

Form: ORION-OE519-RectDmpr-Sub-01B.doc Page 1 of 2DescriptionThe OE519 Rectangular Damper is usedin applications where rectangular duct isspecified or

Seite 18 - Description

Form: ORION-OE519-RectDmpr-Sub-01B.doc Page 2 of 2Using the maximum acceptable velocity for abranch duct (typically 1000-1500 FPM forminimal noise), f

Seite 19 - OE523-XX Round Slaved Zone

Form: Orion--OE736-02-Rect-PDZoneDmpr-Sub-01C.doc Page 1 of 1 Description The OE736-02-VAVZ P.D. Rectangular Damper Kit provides a new solution fo

Seite 20 - Dependent Zone Damper

Form: Orion-OE737-RectBypKit-Sub-01B Page 1 of 1DescriptionThe OE737 Rectangular Bypass Damper Kitmounts to an OE519 Rectangular Damperand controls du

Seite 21

Form: Orion-OE738-RectSlvZoneKit-SUB-01B Page 1 of 1DescriptionThe OE738 Rectangular Slaved-VAV/ZoneDamper Kit provides a new solution for rectan-gula

Seite 22 - Independent Zone Damper

Form: ORION-OE281-04-ProportionalDamper Actuator-1D.doc Page 1 of 1 Description The OE281-04 Proportional Control Damper Actuator is a shaft mount

Seite 23

Form: Orion-OE744-31-VAVZ-ZCAP-Sub-01C.doc Page 1 of 1 Description The OE744-31-VAVZ VAV/Zone Controller Actuator Package with Power/Comm connectors

Seite 24 - OE519 - Rectangular Dampe

Form: Orion-OE282-03-SlvZoneDmprKit-Sub-01A.doc Page 1 of 1 Description The OE282-03 Slaved VAV/Zone Damper Kit consists of an OE282 Damper Actuato

Seite 25

VAV/Zone Cable Length Worksheet Project Name: _____________________________________________ Local Loop Number: ______________________ Directions: Esti

Seite 26 - P.D. Rectangular Damper Kit

VAV/Zone Cable Length Worksheet Project Name: _____________________________________________ Local Loop Number: ______________________ Directions: Esti

Seite 27 - Damper Kit

VAV/Zone Worksheet Form: ORION-VAVZoneWorksheet1B.doc Page 1 of 8 Project Name: _____________________________________________ Local Loop Number: __

Seite 28 - Rectangular Damper Kit

VAV/Zone Worksheet Form: ORION-VAVZoneWorksheet1B.doc Page 2 of 8 Project Name: _____________________________________________ Local Loop Number: __

Seite 29 - Damper Actuator

VAV/Zone Worksheet Form: ORION-VAVZoneWorksheet1B.doc Page 3 of 8 Project Name: _____________________________________________ Local Loop Number: __

Seite 30 - Slaved VAV/Zone Dam

VAV/Zone Worksheet Form: ORION-VAVZoneWorksheet1B.doc Page 4 of 8 Project Name: _____________________________________________ Local Loop Number: __

Seite 31 - Page 1 of 2

VAV/Zone Worksheet Form: ORION-VAVZoneWorksheet1B.doc Page 5 of 8 Project Name: _____________________________________________ Local Loop Number: __

Seite 32 - Page 2 of 2

VAV/Zone Worksheet Form: ORION-VAVZoneWorksheet1B.doc Page 6 of 8 Project Name: _____________________________________________ Local Loop Number: __

Seite 33 - VAV/Zone Worksheet

VAV/Zone Worksheet Form: ORION-VAVZoneWorksheet1B.doc Page 7 of 8 Project Name: _____________________________________________ Local Loop Number: __

Seite 34

Form: Orion-OE744-32-VAVZ-ZCAP-Sub-01B.doc Page 1 of 1 Description The OE744-32-VAVZ VAV/Zone Controller Actuator Package with Terminal Block connec

Seite 35

VAV/Zone Worksheet Form: ORION-VAVZoneWorksheet1B.doc Page 8 of 8 Project Name: _____________________________________________ Local Loop Number: __

Seite 36

Form: ORION-OE325-01-4RelayW-AnalogOutputExpBrd-1B.doc Page 1 of 1 Description The OE325-01 4 Relay with Analog Output Expansion board is used in

Seite 37

Form: ORION-OE282-ProportionalDamper Actuator-1C.doc Page 1 of 1 Description The Orion OE282 Damper Actuator is a shaft mounted, floating point c

Seite 38

Form: ORION-OE282-01ZoneDmprAct-Sub-01A.doc Page 1 of 1 Description The OE282 Damper Actuator is a shaft mounted, floating point control actuator.

Seite 39

Form: Orion-OE520XX-M-RndDmpr-Sub-01G Page 1 of 2 Description The OE520-XX-M Round Pressure Dependent Zone Damper Assembly with modular connectors

Seite 40

Form: Orion-OE520XX-M-RndDmpr-Sub-01G Page 2 of 2 Zone Damper Sizing Use a load program to determine the peak load for each zone. These calculation