SA Controller Operator Interface
System Con guration
15
VAV and CAV Con gurations
Application Con gurations
This area of the manual is designed to simplify the programming setup
process for typical AAON
®
units that have factory installed SA Con-
trollers. Special applications are also included to guide you through
the setup process for more complicated con gurations. The following
con gurations will step you through the Con guration Section of this
manual. Not all con guration screens are listed in this section. This sec-
tion is more of a quick setup guide for basic applications. Please read
each description under the corresponding Con guration Screen in this
manual to see if that option applies to your application. Setpoints are
not shown here since they are not necessarily con guration- speci c,
but are based more on job requirements. Read the descriptions under
the corresponding Setpoint Screens in this manual to understand which
setpoints to use and what values are appropriate to enter.
VAV Unit
If you need to set up your HVAC unit for VAV operation, use the fol-
lowing values:
Con guration Section
Screen #1—Duct Static Pressure Control = “YES”
Screen #3—HVAC Mode Enable = “Supply Air”
Screen #4—HVAC Reset Source = “No Reset”
Can be con gured for Reset; see the Supply Air Setpoint Reset
section that follows before con guring.
Screen #9—Entering Air Humidity Sensor = “YES”
Only if equipped with an Entering Air Humidity Sensor for
Control of Economizer.
Screen #12—Water Side Economizer Control = “YES”
Only if equipped with a Water Side Economizer.
Screen #14—Proof of Flow Input = “YES”
Only if equipped with a Proof of Flow switch.
Screen #28—Emergency Shutdown Input = “YES”
Only if a Smoke Detector, Firestat, or other Shutdown device is
connected to the SA.
Screens #29 through #34 = “YES”
Only needed when connected to Orion VAV/Zone Controllers.
Screens #41 through #60 = Refer to the AAON
®
wiring diagram
inside the unit before con guring on-board and expansion board
relays.
CAV Unit
If you need to set up your HVAC unit for CAV operation, use the fol-
lowing values:
Con guration Section
Screen #1—Duct Static Pressure Control = “NO”
Screen #2—Supply Fan Cycle Mode = “NO”
Only con gure as “YES” if the Supply Fan needs to be off when
no Heating, Cooling, or Dehumidi cation demand exists.
Screen #3—HVAC Mode Enable = “Space Temperature”
For cooling-only VAV units, select “Supply Air.”
Screen #4—HVAC Reset Source = “No Reset”
Can be con gured for Reset; see the Supply Air Setpoint Reset
section that follows before con guring.
Screen #6—Dehumidi cation Control = “YES”
Only if the unit is equipped for Dehumidi cation.
Screen #7—Dehumidi cation Priority = “YES”
Screen #8—Dehumidi cation Unoccupied = “YES”
Only if Dehumidi cation is needed during the Unoccupied
Mode.
Screen #9—Entering Air Humidity Sensor = “YES”
Only if equipped with an Entering Air Humidity Sensor for
Control of Economizer.
Screen #10—Indoor Humidity Sensor = “YES”
Only if equipped with an Indoor Humidity Sensor for
Dehumidi cation.
Screen #12—Water Side Economizer Control = “YES”
Only if the unit is equipped with a Water Side Economizer.
Screen #14—Proof of Flow Input = “YES”
Only if equipped with a Proof of Flow Switch.
Screen #28— Emergency Shutdown Input = “YES”
Only if a Smoke Detector, Firestat, or other Shutdown device is
connected to the SA Controller.
Screens #41 through #60 = Refer to the AAON
®
wiring diagram
inside the unit before con guring on-board and expansion board
relays.