Programming
19
HB Controller Technical Guide
Condenser Fan Deactivation Temperature
The Condenser Fan Deactivation Temperature is a factory setting and
should not be changed unless authorized to do so by WattMaster or
AAON
®
Technical Support.
Auto Stage-Up Time
Description Min. Default Max.
Auto Staging Up Delay 180 Sec 600 Sec 900 Sec
The Auto Stage-Up Time can be adjusted on this screen when you are
using a single-stage thermostat with a multi-stage HB unit.
Heating Module Status Screens
The Heating Module Status Screens are accessed by navigating to the
Heating Module screen and pressing the ENTER key. The following
screen will then appear:
Select “Status” by pressing the ENTER key. Press the up and down
SELECT arrow keys to move forward and backward through the Heat-
ing Module Status screens.
Heating Stage 1 Energized
Line #2 displays “YES” if there is a 24 VAC signal on HB Controller
terminal “W1.”
Heating Stage 2 Energized
Line #2 displays “YES” if there is a 24 VAC signal on HB Controller
terminal “W2.”
Low Pressure Switch Delay
Description Min. Default Max.
Low Pressure Delay Period 5 Sec 30 Sec 60 Sec
The Low Pressure Switch Delay time is a factory setting and should
not be changed unless authorized to do so by WattMaster or AAON
®
Technical Support.
Low Pressure Switch Safety Delay
Description Min. Default Max.
Low Pressure Safety 5 Sec 5 Sec 30 Sec
The Low Pressure Switch Safety Delay time is a factory setting and
should not be changed unless authorized to do so by WattMaster or
AAON
®
Technical Support.
LPS Maximum Trips
Description Min. Default Max.
Low Pressure Max. Trip Point 1 3 5
The Low Pressure Switch Max Trips is a factory setting and should
not be changed unless authorized to do so by WattMaster or AAON
®
Technical Support.
Cooling Fan Off Delay
Description Min. Default Max.
Fan Off Delay Period 1 Sec 45 Sec 120 Sec
The Cooling Fan Off Delay is a factory setting and should not be
changed unless authorized to do so by WattMaster or AAON
®
Techni-
cal Support.
Condenser Fan Activation Temperature
The Condenser Fan Activation Temperature is a factory setting and
should not be changed unless authorized to do so by WattMaster or
AAON
®
Technical Support.
Programming with the HB Service Tool