Zone
Zone
MUA II CONTROLLER CONFIGURATION
VAV/CAV/MUA Operator Interface SD
42
MUA II Con guration Screen Index
MUA II Con guration Screen Index
The available Con guration Screens for the MUA II Controller are
listed on the next few pages by sequential screen number. When the
Unit Controller is con gured for the rst time, it is best to start with
screen #1 and proceed to each screen in numerical order until you have
viewed all available Con guration Screens. This ensures that you have
seen all the available Controller con guration possibilities and have the
opportunity to change or accept the defaults for each screen.
Once the unit is con gured and you decide to change one of the screen
options, it is helpful to know what screen number contains the con gu-
ration you wish to change. With this in mind, the following is a list of
all the MUA II Con guration Screens in numerical order with a brief
listing of the con guration feature available on each screen.
Screen #1 Proof of Flow Switch Installed
Screen #2 OA Humidity Sensor Installed
Screen #3 Heat in Dehumidify Installed
Screen #4 If External Heat, Output Range
Screen #5 Is External Heat Reverse Action
Screen #6 Broadcast Outside Temperature
Screen #7 Broadcast Humidity Reading
Screens #8-27 Relay Con guration Relays 2-21
Modular Service Tool Instructions
No matter what screen or menu you’re in, press <CONFIGURATION>.
The Unit Selection Screen will appear, shown below, requesting that you
enter the unit ID number.
Unit Selection*00*
Enter Unit ID#
Selected ID#: XXXX
Enter the correct unit ID number of the Unit Controller you want to
con gure and then press <ENTER>. Once communication is established,
the *00* message will go away. Then
press <>. You will then see
Unit Con guration Screen #1. Press
<ENTER> to save entered data
and
press <> to scroll through the screens.
NOTE: If the *00* remains, it indicates a communication failure
to the controller.
System Manager SD Instructions
From any Main screen, press <SETPOINTS>. The screen below will
appear because this option requires passcode clearance. Only a Level 2
passcode can change setpoints.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
If the correct passcode was entered, the Unit Selection Screen will be
displayed.
Unit Selection*00*
Enter Unit ID#
Selected ID#: XXXX
Enter the Unit ID of the controller you wish to change schedules for and
press
<ENTER>. Once communication is established, the *00* message
will go away. Then
press <>.
NOTE: If the *00* remains, it indicates a communication
failure to the controller.
The following screen will be displayed:
Change Setpoints
Configure Unit
Save/Copy/Restore
Scroll down to the ‘Con gure Unit’ option and press <ENTER>. This
will take you to the rst Con guration Screen shown below.