Operator Interfaces
Technical Guide
45
Setpoint Screen #11
HC Box Spts IDxxxx
Day/Night Schedule
Control #: x
0=AHU 1-7=Scheduler
This screen allows you to set the VAV/Zone controller to operate on a
remote schedule instead of the schedule that is contained in the VCM
controller.
Description Mini mum Default Maxi mum
Schedule Number 0 0 1 to 7
Setpoint Screen #12
HC Box Spts IDxxxx
Maximum Slide Offset
Effect on Spt.: x°F
If the Flush Mount Wall Sensor has the optional Setpoint Slide Adjust,
this is the maximum amount the user can adjust the heating and cooling
setpoints up or down as the slide is moved from the center position to
its full up or down position
Description Minimum Default Maximum
Effect on SP
0
°
F0
°
F6
°
F
Setpoint Screen #13
HC Box Spts IDxxxx
Push-Button Override
Duration : x.x Hr
If the Flush Mount Wall Sensor has the optional Push-Button Override,
this is the amount of the Box Controller will resume using its Occupied
Setpoints during unoccupied mode. This will generate a call for the Air
Handler to start its fan and provide heating or cooling, depending on
how the user configures the Air Handler.
Description Minimum Default Maximum
Duration 0.0 Hr 0.0 Hr 8.0 Hr
Setpoint Screen #14
HC Box Spts IDxxxx
Maximum EMS Setpoint
Offset...: xx°F
This screen is currently not used for this application.
Description Minimum Default Maximum
EMS Setpoint x x x
Setpoint Screen #15
Sensor Calibration
SPC: xxx.x° xxx.x°
SAT: xxx.x° xxx.x°
[SAT Only if Sensor]
The Thermistor Type III sensor readings can be calibrated. Enter a Posi-
tive value to increase a reading and a Negative value to decrease a read-
ing.
Note: The Supply Air Temperature calibration offset only op-
erates on the reading when the Box Controller has it’s’
own Supply Air Temperature sensor installed on the
AUX2 input. If the supply temperature is received from
a global broadcast, you will need to go to the air handler
to calibrate the temperature reading.
Description Minimum Default Maximum
SPC [ Space Temp ]
-100.0°F0.0°F +100.0°F
SAT [ Supply Air ]
-100.0°F0.0°F +100.0°F