Appendix F - SA Controller LON Parameters
SNVTs for the SA Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
Parameter Name Object Description
Limits
Dewpoint
Setpoint
DptSt Analog
Input
If the outdoor
dewpoint rises above
this setpoint, the
unit will activate the
Dehumidifi cation
Demand.
35 80
Occupied/
Mode
Enable
Cooling
Setpoint
OcpClSt Analog
Input
If the control
temperature rises one
degree above this
setpoint, the control
will activate the cool-
ing demand. If the
control temperature
is the Supply Air Sen-
sor, then the cooling
demand is always
active.
099
Occupied/
Mode
Enable
Heating
Setpoint
OcpHtSt Analog
Input
If the control
temperature drops
one degree below
this setpoint,
the control will
activate the heating
demand. If the
control temperature
is the Supply Air
Sensor, then there is
no heating demand.
99
Schedule
Force
SchdFrc Analog
Input
0 = Auto/
Unoccupied Mode
1 = Forced On
2 = Forced Off
02
Space
Sensor
Offset
SpcTpOst Analog
Input
If the Space
Temperature
Sensor is reading
incorrectly, you can
use this option to
enter an offset
temperature to
adjust the Sensor’s
Temperature.
-100 100
SAT
Cooling
Setpoint
SaClSt Analog
Input
Supply Air Setpoint
in Cooling Mode.
40 80
SAT
Heating
Setpoint
SaHtSt Analog
Input
Supply Air Setpoint
in Heating Mode.
40 200
Supply Air
Cool High
Reset
SaClRt Analog
Input
High Supply Air
Cooling Reset Limit
40 150
Supply Air
Heat High
Reset
SaHtRt Analog
Input
High Supply Air
Heating Reset Limit
40 150
Cooling
Low Reset
Source
ClLoRt Analog
Input
Low Cool Reset
Source Setpoint
1 150
SNVTs for the SA Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
Parameter Name Object Description
Limits
Cooling High
Reset Source
ClHiRt Analog
Input
High Cool Reset
Source Setpoint
1 150
Heating Low
Reset Source
HtLoRt Analog
Input
Low Heat Reset
Source Setpoint
1 150
Heating High
Reset Source
HtHiRt Analog
Input
High Heat Reset
Source Setpoint
1 150
Supply Air
Sensor Offset
SaTpOst Analog
Input
If the Supply Air
Temperature Sensor
is reading
incorrectly, you can
use this option to
enter an offset
temperature to
adjust the Sensor’s
Temperature.
-100 100
Warm Up
Setpoint
WmupSt Analog
Input
In a VAV
application, upon
entering the
occupied mode, the
Warm-up Demand
will be activated
if the return air
temperature falls
one degree below
this setpoint.
50 90
Coil
Temperature
Setpoint
CoilTpSt Analog
Input
This is the coil
suction temperature
target during
dehumidifi cation
mode. Produces
dewpoint in the
supply air
approximately 10°F
above this setpoint.
35 70
Indoor
Humidity
Setpoint
InRhSt Analog
Input
If the indoor
humidity rises
above this setpoint,
the unit will
activate the
Dehumidifi cation
Demand.
0 100
Unoccupied
Cooling
Offset
UnClOst Analog
Input
During the
Unoccupied Mode
of Operation, this
Setpoint spreads
the Occupied Cool-
ing Setpoint out by
a user adjustable
amount. If you do
not want Cooling to
operate during the
Unoccupied Mode,
use the default
setting of 30°F for
these setpoints.
030